Maintenance on CanadaBuys website

The CanadaBuys website will be down for scheduled maintenance at the times listed below. We apologize for any inconvenience.  

  • Friday, May 24, 7:00 pm until 11:00 pm (Eastern Time) 

  • Sunday, May 26, 7:45pm until 9:45 pm (Eastern Time) 

Marine Refrigeration & A/C Course

Solicitation number W010X-16C033/A

Publication date

Closing date and time 2015/12/11 13:00 EST


    Description
    Trade Agreement: NAFTA/AIT/Canada FTAs with Peru/Colombia/Panama
    Tendering Procedures: Generally only one firm has been invited to bid
    Non-Competitive Procurement Strategy: Government Objectives Representing Best Interests/Value to Govt
    Comprehensive Land Claim Agreement: No
    Vendor Name and Address: 
    Nova Scotia Community College
    21 Woodlawn Rd
    Dartmouth Nova Scotia
    Canada
    B2W2R7
    Nature of Requirements: 
    
    1. Advance Contract Award Notice (ACAN) 
    An ACAN is a public notice indicating to the supplier community that a department or agency intends to award a contract for goods, services or construction to a pre-identified supplier, thereby allowing other suppliers to signal their interest in bidding, by submitting a statement of capabilities. If no supplier submits a statement of capabilities that meets the requirements set out in the ACAN, on or before the closing date stated in the ACAN, the contracting officer may then proceed with the award to the pre-identified supplier.
    
    2. Definition of the requirement 
    The Department of National Defence has a requirement to provide a Refrigeration and Air Conditioning (A/C) Instructor’s advance course. This course is for Refrigeration and A/C Instructors at Canadian Forces (CF) fleet schools. The course must be delivered by an accredited educational institution located either within the Halifax Regional Municipality, NS or within the Victoria, B.C geographicalarea.
    
    The work will involve the following: the Contractor shall provide a 10-week course for up to 4 students that covers all information and results in course attendees being able to perform all the practical tasks listed in Table 1 below. Training will start in January 2016 and must be completed prior to March 31, 2016. The Contractor will be responsible to provide both classroom and practical, hands-on training. The Contractor shall have training materials and equipment that allow them to instruct all practical aspects of the subject material detailed at Table 1 and supply training materials to students.
    
    3. Criteria for assessment of the Statement of Capabilities (Minimum Essential Requirements) 
    Any interested supplier must demonstrate by way of a statement of capabilities that it meets the following requirements:
    (a) Experience: To teach ALL the following mandatory requirements of the course, the educational institution must be able provide:
    1. a course both in classroom and practical setting;
    2. a written training course curriculum;
    3. all necessary course material, equipment, and facilities; and
    4. a qualified instructor.
    The mandatory course teaching points are listed in Table 1:
    
    TABLE 1- COURSE TEACHING POINTS
    Enabling Objective Specification
    INTRODUCTION TO REFRIGERATION PRINCIPLES (14 periods)
    1.1
    COMPUTE problems involving heat content of water and refrigerants
    1.2
    STATE the effects of various heat on liquids and gases
    1.3
    STATE the various heat transfer terms
    1.4
    STATE the various values representing the correct pressure/temperature relationships, given either pressure or temperature values with the aid of a pressure/temperature chart
    DESCRIPTION OF A MAIN REFRIGERATION SYSTEM (14 periods)
    2.1
    STATE the various values representing the correct pressure/temperature relationships, given either pressure or temperature values with the aid of a pressure/temperature chart
    2.2
    STATE the stages and the pressure areas of a refrigeration cycle
    2.3
    IDENTIFY Main Refrigeration System components as to their function
    2.4
    LOCATE Main Refrigeration System components
    REFRIGERANTS (8 periods)
    3.1
    STATE the characteristics of various refrigerants used in a main refrigeration system
    3.2
    STATE the procedures for refrigerant handling and storage
    3.3
    STATE the first aid procedures for personnel casualties
    3.4
    STATE the operating characteristics of various types of refrigerant leak detectors
    3.5
    STATE the procedure for Main Refrigeration System refrigerant draining using a refrigeration recovery unit
    3.6
    PERFORM, as a group, Main Refrigeration System refrigerant draining using a refrigeration recovery unit, given the necessary MRC, tools, equipment and protective clothing. All personnel and equipment safety precautions must be observed.
    REFRIGERATION SYSTEM COMPONENTS (30 periods)
    4.1
    STATE the operating characteristics of Refrigeration System components
    4.2
    STATE the operating characteristics of a Main Refrigeration System Rotary Compressor
    4.3
    STATE the reactions of a Main Refrigeration System Evaporator Pressure Regulating (EPR) valve to various changes in system conditions
    4.4
    STATE the reactions of a Main Refrigeration System Thermostatic Expansion Valve (TXV) to various changes in system conditions
    4.5
    STATE the reactions of a Main Refrigeration System Water Regulating Valve (WRV) to various changes in system conditions
    4.6
    STATE the procedures for Main Refrigeration System testing pressure switches and safety devices
    4.7
    PERFORM MainRefrigeration System pressure switches and safety devices testing.
    4.8
    STATE the appropriate safety precautions to be followed when performing Main Refrigeration System pressure switches and safety devices testing
    OPERATING A MAIN REFRIGERATION SYSTEM (6 periods)
    5.1
    STATE the procedures for starting a Main Refrigeration System
    5.2
    STATE the procedures for securing a Main Refrigeration System
    5.3
    STATE the appropriate safety precautions to be followed while operating a Main Refrigeration System
    5.4
    PERFORM starting procedures for a Main Refrigeration System
    5.5
    PERFORM securing procedures for a Main Refrigeration System
    MAIN REFRIGERATION SYSTEM PREVENTATIVE MAINTENANCE (28 periods)
    6.1
    PERFORM as a group a Main Refrigeration System purging given the necessary tools, equipment and protective equipment
    6.2
    STATE the health and environmental effects when not using a refrigeration recovery unit for a Main Refrigeration System
    6.3
    STATE the procedure for Main Refrigeration System compressor lube oil renewal
    6.4
    STATE the procedure for Main Refrigeration System leak testing
    6.5
    PERFORM as a group Main Refrigeration leak testing and state procedures given the necessary tools, equipment and protective equipment
    6.6
    STATE the procedure for Main Refrigeration System refrigerant charging
    6.7
    PERFORM as a group Main Refrigeration System refrigerant charging given the necessary tools, equipment and protective equipment and state appropriate procedures
    6.8
    STATE the conditions of Main Refrigeration System compressor lube oil quality that requires renewal of the lube oil
    6.9
    STATE the operating characteristics of a compressor capacity control system
    6.10
    STATE the responses of a compressor capacity control system (Carrier or York) to changes in the Main Refrigeration System conditions
    HOT GAS DEFROST (3 periods)
    7.1
    STATE the appropriate safety precautions to be followed while operating a Main Refrigeration System with 100 % accuracy
    7.2
    STATE the procedures for Hot Gas Defrosting
    7.3
    PERFORM as a group Hot Gas Defrosting on a Main Refrigeration System and state appropriate safety procedures
    7.4
    STATE operating characteristics of a unit coil using electric heat strips and defrost timer
    MAIN REFRIGERATION SYSTEM CORRECTIVE MAINTENANCE (38 periods)
    8.1
    STATE the operating characteristics of an Evaporator Pressure Regulating (EPR) valve
    8.2
    STATE the procedure for the adjustment of an Evaporator Pressure Regulating (EPR)
    8.3
    STATE the operating characteristics of a Water Regulating Valve
    8.4
    STATE the procedure for adjusting a Water Regulating Valve (WRV)
    8.5
    STATE the operating characteristics of a Thermostatic Expansion Valve (TXV)
    8.6
    STATE the procedure for adjusting a Thermostatic Expansion Valve (TXV)
    8.7
    TROUBLESHOOT a Main Refrigeration System given operating logs and imposed problems on the system
    8.8
    PERFORM as a group adjustments of Evaporator Pressure Regulator (EPR), Water Regulating Valve (WRV), and Thermostatic Expansion Valve (TXV)
    8.9
    STATE the symptoms of Main Refrigeration System common operational problems
    8.10
    STATE the causes of Main Refrigeration System common operational problems
    8.11
    STATE typical corrective actions taken in solving Main Refrigeration System operational problems
    8.12
    STATE the effects of various conditions of heat, load and stowage of a Main Refrigeration System
    8.13
    STATE the functions of internal parts of a Main Refrigeration System Compressor
    8.14
    STATE the appropriate safety precautions to be followed when performing corrective maintenance on a Main Refrigeration System
    8.15
    PERFORM as a group adjusting procedures for a Thermostatic Expansion Valve (TXV)
    8.16
    PERFORM as a group adjusting procedures for a Water Regulating Valve (WRV)
    8.17
    PERFORM as a group adjusting procedures for an Evaporator Pressure Regulator (EPR)
    SILVER BRAZING (18 periods)
    9.1
    BRAZE hermetic units piping in accordance with silver brazing techniques. The silver brazed hermetic system piping must hold 100 PSIG low-pressure air for l minute.
    9.2
    STATE the correct procedures for silver brazing
    9.3
    STATE the safety precautions to be observed while silver brazing various piping systems
    9.4
    STATE the various types of alloys to be used in silver brazing hermetic systems
    9.5
    STATE the appropriate safety precautions to be followed when performing corrective maintenance on various hermetic systems with 100 % accuracy
    9.6
    STATE the procedures for flaring copper tubing on hermetic units
    INTRODUCTION TO HERMETIC UNITS (26 periods)
    10.1
    STATE the functions of a hermetic refrigeration unit
    10.2
    STATE the correct operating characteristics of a capillary tube hermetic refrigeration unit
    10.3
    STATE the correct operating characteristics of a Thermostic Expansion Valve (TXV)
    10.4
    STATE the factors affecting air cooled condenser performance when used on a hermetic unit in accordance with Refrigeration and Air Conditioning Technology, ISBN 0-7668-0667-7
    10.5
    STATE the correct operational characteristics of a single phase electric motor and their control devices in accordance with Refrigeration and Air Conditioning Technology, ISBN 0-7668-0667-7
    10.6
    STATE the correct operational characteristics of a hermetic compressor in accordance with Refrigeration and Air Conditioning Technology, ISBN 0-7668-0667-7
    REACH IN REFRIGERATOR (4 periods)
    11.1
    OPERATE/MONITOR a reach-in refrigerator and state the appropriate safety procedures
    11.2
    STATE the functions of the refrigeration components of a reach-in refrigerator
    11.3
    STATE the correct electrical components related to operating characteristics of a reach-in refrigerator
    11.4
    STATE the appropriate safety precautions to be followed while operating hermetic units
    ICE MACHINES (6 periods)
    12.1
    STATE the functions of various components of a hermetic ice maker
    12.2
    OPERATE/MONITOR hermetic ice maker
    12.3
    STATE the electrical components related to operating characteristics of a hermetic ice maker
    12.4
    STATE the operating characteristics of a hermetic ice maker
    12.5
    STATE the appropriate safety precautions to be followed while operating hermetic ice maker given a set of alternatives with 100 % accuracy
    SALAD BAR/COUNTER DISPLAY CASE (3 periods)
    13.1
    STATE the electrical components related tothe operating characteristics of the salad counter display case
    13.2
    STATE the operating characteristics of the salad counter display case given a set of alternatives
    13.3
    OPERATE/MONITOR a hermetic salad counter display case
    13.4
    STATE the appropriate safety precautions to be followed while operating hermetic units
    SELF CONTAINED AIR CONDITIONING UNIT (SCAC) (12 periods)
    14.1
    STATE the function of the refrigeration components of a hermetically packaged air conditioning unit
    14.2
    STATE the electrical components related to operating characteristics of a hermetically packaged air conditioning unit
    14.3
    STATE the operating characteristics of a hermetically packaged air conditioning unit
    14.4
    OPERATE/MONITOR a package air conditioning unit
    14.5
    STATE the operating characteristics of a hermetically packaged air conditioning unit
    14.6
    STATE the appropriate safety precautions to be followed while operating hermetic units
    PREVENTATIVE MAINTENANCE ON HERMETIC UNITS (6 periods)
    15.1
    CLEANan air cooled condenser given the necessary Tech manuals, tools and equipment
    15.2
    CLEAN as a group an evaporator cooling coil given the necessary Tech Manuals, tools and equipment
    15.3
    STATE the appropriate safety precautions to be followed while performing preventive maintenance
    CORRECTIVE MAINTENANCE ON HERMETIC UNITS (29 periods)
    16.1
    TROUBLESHOOT a hermetic unit
    16.2
    STATE the causes of operational problems on a reach-in refrigerator
    16.3
    STATE the causes of operational problems on a hermetic ice maker
    16.4
    STATE the causes of operational problems on a hermetic salad counter display case
    16.5
    STATE the causes of operational problems on a hermetically packaged air conditioning unit
    16.6
    PERFORM electrical components analysis usinga HA1 hermetic analyzer
    16.7
    PERFORM electrical components analysis using a HA1 hermetic analyzer
    16.8
    REPLACE a malfunctioning component on a hermetic unit given the necessary technical manuals, tools, equipment and repair parts
    16.9
    STATE the appropriate safety precautions to be followed while performing corrective maintenance on a hermetic unit
    AIR MEASUREMENT (2 Periods)
    17.1
    MEASURE relative humidity, dry bulb temperature, wet bulb temperature and dew point
    17.2
    STATE the procedure for measuring relative humidity, dry bulb temperature, wet bulb temperature and dew-point temperature
    CENTRIFUGAL AIR CONDITIONING PREVENTATIVE MAINTENANCE (2 periods)
    18.1
    TROUBLESHOOT a centrifugal air conditioning system given simulated operational problems, pressure/ temperature conversion charts and operating centrifugal air conditioning system log
    18.2
    STATE the causes of centrifugal air conditioning system problems given a set of alternatives
    OPERATING A CENTRIFUGAL AIR CONDITIONING SYSTEM (2 periods)
    19.1
    OPERTATE the operating characteristics of a centrifugal air conditioning system
    19.2
    PERFORM as a group starting and securing procedures for operating a centrifugal air conditioning system
    19.3
    OPERATE a centrifugal air conditioning universal microprocessor control
    PURGE AND PUMPOUT AND TURBOGUARD PURGE UNITS (5 periods)
    20.1
    STATE the function of the components of a centrifugal air conditioning system purge and pump out unit
    20.2
    STATE the operating characteristics of the centrifugal air conditioning system purge and pump out unit
    20.3
    STATE the function of the centrifugal air conditioning system purge unit
    CENTRIFUGAL AIR CONDITIONING SYSTEM CORRECTIVE MAINTENANCE (11 periods)
    21.1
    TROUBLESHOOT a centrifugal air conditioning system given simulated operational problems, pressure/temperature conversion charts and operating centrifugal air conditioning system log sheets
    21.2
    STATE the causes of centrifugal air conditioning system problems
    CENTRIFUGAL AIR CONDITIONING SYSTEM UNIVERSAL MICROPROCESSOR CONTROL PANEL (5 periods)
    22.1
    STATE the stages of a centrifugal air conditioning system.
    22.2
    IDENTIFY centrifugal air conditioning system components as to their functions, given a list of components and functions.
    22.3
    IDENTIFY the components of a Universal Microprocessor Control Panel as to their operating Characteristics and functions
    22.4
    ALTER program parameters using microprocessor control panel menu options
    22.5
    INSERT current date/time using menu options into the microprocessor panel
    22.6
    STATE the operational controls and components of a Microprocessor Control Panel and general description of Inputs/Outputs and associated sensors as related to their operating characteristics and functions, given a listof alternatives.
    22.7
    STATE the appropriate safety precautions to be followed while operating a Universal Microprocessor Control Panel, with 100 % accuracy
    22.8
    STATE the appropriate display screens on a Microprocessor Control Panel to their function, given a list of alternatives
    22.9
    STATE the possible shutdown conditions controlled by the Microprocessor Control
    CENTRIFUGAL AIR CONDITIONING SYSTEM MICROPROCESSOR CONTROLLED CENTRIFUGAL TROUBLESHOOTING AND DIAGNOSTICS (5 periods)
    23.1
    STATE thetypes of built-in tests performed by the Microprocessor Control Panel, given a list of alternatives.
    23.2
    IDENTIFY the components provided in a Maintenance Assist Module (MAM's) Kit as to their function.
    23.3
    IDENTIFY the components of a Universal Microprocessor Control Panel as to their operating characteristics and functions
    23.4
    STATE the appropriate safety precautions to be followed while operating a Universal Microprocessor Control Panel
    23.5
    STATE the appropriate safety precautions to be followed while performing preventive maintenance
    23.6
    STATE the appropriate safety precautions to be followed while operating a Universal Microprocessor Control Panel
    23.7
    EXECUTE Built-In Test using the microprocessor control panel menu options.
    23.8
    STATE the function of a thermistor as to its use on a centrifugal air conditioning system
    23.9
    STATE the function of various display screens on a microprocessor control panel
    23.10
    STATE the possible shutdown conditions controlled by the microprocessor control panel
    23.11
    DEMONSTRATE operational and functional knowledge of the Microprocessor Control Panel by effectively diagnosing panel and/or system failures.
    23.12
    IDENTIFY and DEMONSTRATE the use of the External Diagnostic System in evaluating troubleshooting and data logging.
    23.13
    IDENTIFY pre-annunciator alarm parameters as to the pressure transducer and/ or thermistor
    RECIPROCATING AIR CONDITIONING SYSTEMS (13 periods)
    24.1
    IDENTIFY electrical components in the starting circuit of a reciprocating air conditioning system given sets of alternatives
    24.2
    STATE the operating characteristics of a reciprocating air conditioning system
    24.3
    IDENTIFY electrical components of a reciprocating air conditioning system as to their function given a reciprocating air conditioning system electrical schematic and a list of functions
    24.4
    IDENTIFY the components of a chilled water system that interface with a reciprocating air conditioning system
    24.5
    STATE the appropriate safety precautions to be followed while operating a reciprocating air conditioning system
    RECIPROCATING AIR CONDITIONING SYSTEM PROGRAMMABLE LOGIC
    CONTROLLER (6 periods)
    25.1
    IDENTIFY electronic components of a programmable logic controller and their functions, given an electrical schematic and a list of functions
    25.2
    IDENTIFY the digital read-out codes of a programmable logic controller given a list of possible error codes
    25.3
    STATE the appropriate safety precautions to be followed while operating a reciprocating air conditioning system
    25.4
    PERFORM, as a group, startup and securing a reciprocating air conditioning system
    PREVENTATIVE/CORRECTIVE MAINTENANCE (12 periods)
    26.1
    TROUBLESHOOT a reciprocating air conditioning system
    26.2
    STATE the repairprocedures for a reciprocating air conditioning system
    26.3
    STATE the symptoms of a reciprocating air conditioning system problems
    26.4
    STATE the appropriate safety precautions to be followed while performing corrective maintenance on air conditioning systems
    CENTRIFUGAL AIR CONDITIONING SYSTEM (4 periods)
    27.1
    STATE the stages of a centrifugal air conditioning system
    27.2
    IDENTIFY centrifugal air conditioning system components and their functions
    27.3
    DESCRIBE the characteristics of variousrefrigerants used in a centrifugal air conditioning system
    27.4
    DESCRIBE the similarities and differences of a reciprocating and a centrifugal air conditioning system
    CENTRIFUGAL AIR CONDITIONING SYSTEM COMPRESSOR (10 periods)
    28.1
    IDENTIFY internal parts of a centrifugal air conditioning system
    28.2
    STATE the function of internal parts of a centrifugal air conditioning system motor and compressor
    28.3
    IDENTIFY the components of a centrifugal air conditioning system compressor lubrication system and their operating characteristics and functions
    28.4
    DISASSEMBLE, inspect, reassemble as a group a centrifugal air conditioning system compressor, as a group
    ELECTRICAL COMPONENTS AND CIRCUITY FOR A CENTRIFUGAL AIR
    CONDITIONING SYSTEM (6 periods)
    29.1
    IDENTIFY electronic components in the starting circuit of a centrifugal air conditioning system given an electrical schematic
    29.2
    IDENTIFY electronic components of a centrifugal air conditioning system as to their function given an electricalschematic
    CAPACITY CONTROL SYSTEM (PNEUMATIC AND ELECTRONIC) (2 periods)
    30.1
    STATE the function of components in the pneumatic capacity control system for a centrifugal air conditioning system
    30.2
    STATE the function of components in the electronic capacity control system for a centrifugal air conditioning system, given a set of alternatives
    30.3
    DESCRIBE the electronic capacity control system of a centrifugal air conditioning system during heat load changes given a set of alternatives
    
    (b) Academic qualifications of Instructor:
    Refrigeration instructor(s) must be certified to instruct in accordance with Heating Refrigeration and Air Conditioning Institute of Canada (HRAI) requirements.
    
    (c) Professional designation, accreditation, and/orcertification: The institution delivering the course shall be a certified Canadian College.
    
    4. Applicability of the trade agreements to the procurement 
    This procurement is subject to the following trade agreements:
    o Agreement on Internal Trade (AIT)
    o North American Free Trade Agreement (NAFTA)
    
    5. Justification for the Pre-Identified Supplier 
    The supplier selected in advance and identified in section 10, Nova Scotia Community College (NSCC), is to our knowledge the only supplier meeting all the specifications required in the section 3.
    
    Nova Scotia Community College has been the sole provider of this service for several years for instructors from the Canadian Forces Naval Engineering School (CFNES) in Halifax, NS and the Canadian ForcesFleet School (CFFSE) in Esquimalt, BC. NSCC possess the required knowledge, experience, and capabilities. Under a previous contract, NSCC developed the pilot Marine Refrigeration and Air Conditioning Instructor training course for the specific requirements of the Department of National Defence (DND), Maritime Forces Atlantic and have been providing the training to DND since 2005. NSCC owns the copy write for the Marine Refrigeration and Air Conditioning Instructor training course curriculum. NSCC has acquired the refrigeration equipment which meets the course standard. This equipment is specific to naval regulation and infrastructures. NSCC is located in the Halifax Regional Municipality. NSCC has the infrastructure, equipment, and faculty expertise required to provide this training.
    
    6. Government Contracts Regulations Exception 
    The following exception to the Government Contracts Regulations is invoked for this procurement under subsection 6(d) - only one person is capable of performing the work.
    
    7. Exclusions and/or Limited Tendering Reasons
    The following exclusions and/or limited tendering reasons are invoked:
    Agreement on Internal Trade (AIT) - Article 506.12 (b)
    North American Free Trade Agreement (NAFTA) - Article 1016.2 (b)
    
    8. Period of the proposed contract or delivery date
    The proposed contract is from date of award to March 31, 2016.
    
    9. Cost estimate of the proposed contract
    The estimated value for this notice is in the following cost category: between $80,000.00 and $100,000.00 (applicable taxes included).
    
    10. Name and address of the pre-identified supplier 
    Nova Scotia Community College
    21 Woodlawn Rd.
    Dartmouth, NS
    B2W 2R7
    
    11. Suppliers' right to submit a statement of capabilities 
    Suppliers who consider themselves fully qualified and available to provide the goods, services or construction services described in the ACAN may submit a statement of capabilities in writing to the contact person identified in this notice on or before the closing date of this notice. The statement of capabilities must clearly demonstrate how the supplier meets the advertised requirements.
    
    12. Closing date for a submission of a statement of capabilities 
    The closing date and time for accepting statements of capabilities is: 2:00 p.m. AST, Friday, December 11, 2015.
    
    13. Inquiries and submission of statements of capabilities
    Laila Figueredo
    Supply Specialist
    Public Works and Government Services Canada
    Atlantic Region - Acquisitions Branch
    1713 Bedford Row
    Halifax, Nova Scotia
    B3J 3C9
    Telephone: (902) 496-5353
    Facsimile: (902) 496-5016
    E-mail address: laila.figueredo@pwgsc-tpsgc.gc.ca
    Delivery Date: Above-mentioned
    
    You are hereby notified that the government intends to negotiate with one firm only as identified above. Should you have any questions concerning this requirement, contact the contracting officer identified above.
    
    An Advance Contract Award Notice (ACAN) allows departments and agencies to post a notice, for no less than fifteen (15) calendar days, indicating to the supplier community that it intends to award a good, service or construction contract to a pre-identified contractor. If no other supplier submits, on or before the closing date, a Statement of Capabilities that meets the requirements set out in the ACAN, the contracting authority may then proceed with the award.  However, should a Statement of Capabilities be found to meet the requirements set out in the ACAN, then the contracting authority will proceed to a full tendering process.
    
    Suppliers who consider themselves fully qualified and available to provide the services/goods described herein, may submit a statement of capabilities in writing to the contact person identified in this Notice on or before the closing date of this Notice. The statement of capabilities must clearly demonstrate how the supplier meets the advertised requirements.
    
    The PWGSC file number, the contracting officer's name and the closing date of the ACAN must appear on the outside of the envelope in block letters or, in the case of a facsimile transmission, on the covering page.
    
    The Crown retains the right to negotiate with suppliers on any procurement.
    
    Documents may be submitted in either official language of Canada.

    Contract duration

    Refer to the description above for full details.

    Trade agreements

    • Canada-Panama Free Trade Agreement
    • Agreement on Internal Trade (AIT)
    • Canada-Colombia Free Trade Agreement
    • Canada-Peru Free Trade Agreement (CPFTA)
    • North American Free Trade Agreement (NAFTA)

    Partner with another business

    The functionality to add your company name to the list of interested businesses is temporarily unavailable.

    This list does not replace or affect the tendering procedures for this procurement process. Businesses are still required to respond to bid solicitations, and to compete based on the set criteria. For more information please read the Terms of use.

    Contact information

    Contracting organization

    Organization
    Public Works and Government Services Canada
    Address
    11 Laurier St, Phase III, Place du Portage
    Gatineau, Quebec, K1A 0S5
    Canada
    Contracting authority
    Figueredo, Laila
    Phone
    (902) 496-5353 ( )
    Fax
    (902) 496-5016
    Address
    1713 Bedford Row
    Halifax, Nova Scot, B3J 3C9

    Buying organization(s)

    Organization
    Department of National Defence
    Address
    101 Colonel By Dr
    Ottawa, Ontario, K1A0K2
    Canada
    Bidding details

    Details for this tender opportunity are provided in the Description tab.

    Please contact the contracting officer to get the full solicitation documentation, access information on how to bid, or if you have any questions regarding this tender opportunity.

    Note that there may be fees to access the documents or bid. These should be outlined in the Description tab.

    We recommend that you contact the contracting officer as soon as possible, as there may be deadlines for receiving questions.

    Eligibility and terms and conditions

    Government of Canada tender and awards notices, solicitation documents, and other attachments are fully accessible and available free of charge and without having to register on CanadaBuys.

    Information may be available on another source prior to being available on CanadaBuys. You may have received this information through a third-party distributor. The Government of Canada is not responsible for any tender notices and/or related documents and attachments not accessed directly from CanadaBuys.canada.ca.

    Government of Canada tender or award notices carry an OpenGovernment License - Canada that governs its use. Related solicitation documents and/or tender attachments are copyright protected. Please refer to our terms and conditions page for more information.

    Summary information

    Notice type
    Advance Contract Award Notice
    Language(s)
    English, French
    Region(s) of delivery
    British Columbia
    ,
    Nova Scotia
    Procurement method
    Non-Competitive
    Selection criteria
    Consulting Services Regarding Matters of a Confidential Nature
    Commodity - GSIN
    Click the links below to see a list of notices associated with the GSIN codes.

    Support for small and medium businesses

    If you have questions about this tender opportunity, please contact the contracting officer, whose information is found in the Contact information tab. 

    Refer to our Support page if you need help or have questions about the government procurement process, including how to bid or how to register in SAP Ariba. You can also contact Procurement Assistance Canada, which has offices across Canada.

     

    Date modified: